Please provide elevations plans that show the existing structure with the addition.

5/19/2008 JNP

Please provide a floor plan showing the existing room that will adjoin the study. NOTE: Bedroom emergency egress must go directly to the exterior and not pass through another area per R310.

5/19/2008 JNP

Please provide detail for the deck railing to comply with R312.

5/19/2008 JNP

Please provide a fastening schedule for all the uplift connections shown on the plans.

5/19/2008 JNP

Please provide a DEP permit or a letter from DEP that states a permit is not required.

5/19/2008 JNP