1) Incomplete review, provide following information. 11/23/2004 JDC
2) Truss plate evaluation report by ICC Evaluation Services, (ICBO evaluations no longer in existance) ER-2929, states that the plates indicated in the drawings must be pressed in place. Please provide truss manufacturers engineering for Roof Trusses and Rafters and provide calculations for the loads associated with the rafters and trusses. 11/23/2004 JDC
3) Indicate the size and frequency of the fasteners used in the main laminated columns. 11/23/2004 JDC