SJC Home
Clearance Sheet R1998-001122*003

 Department IssuesSigned OffIntl

1. This project appears to have been submitted after January 1st, 2018 which would require all dated documents to list the 2017 FBC reference. Please update all documents which shall include, Architectural, Engineering, Trusses, and Florida Energy.

Plan review halted. 

 

2. Please review the Florida Product approval number for the Standing Seam Metal roof product. FL. #1832.2 appears to be for red-iron metal building installation.

 
3. General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal.
If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again.
ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
 
4. Pen and ink changes, white-outs, or any such altering of raised seal engineering drawings, is not permitted under state laws governing the practice of Architecture or Engineering. All information on the raised seal drawings must part of the printed sheets at the time the drawings are sealed by the Architect/Engineer.