Clearance Sheet R1998-000201*002

 Department IssuesSigned OffIntl

Pool Safety Features: Please identify the pool safety features, a requirement of this pool permit, (i.e. screen enclosure with door & window alarms, baby barrier fence, fence with water alarms…). This is a requirement for every pool and should be either identified on the pool layout drawing or on the site plan.(FBC-R4501.17.2) PLEASE SPECIFY WHICH TYPE OF ALARMS, DOOR & WINDOW OR WATER ALARM.

7/8/2019 dking

Missing Product Info:  Please provide pertinent product information sufficient to verify installation requirements for the proposed filter and pool heater, ( Identify by circling on the manufacturers product sheets submitted or list on the pool layout sheet or similar method. Including manufacturer and model number identification).

7/8/2019 dking

PLEASE PROVIDE A LEGIBLE POOL LAYOUT DRAWING: Provide a representative dimensioned layout drawing of the pool & spa including depth of the pool. (FBC-R107.2.1 & 107.2.5)

7/8/2019 dking

POOLS: In-ground and aboveground pools shall be designed to withstand all flood related loads and load combinations.

Pools in a ‘VE’ Flood Zone: Pools in coastal high-hazard areas shall be designed and constructed in conformance with ASCE 24 (per FBC-R322.3.3.1). In-ground and above ground pools shall be designed to withstand all flood-related loads and load combinations. (Engineering required)

 

NOTE: NEW POOL BEING CONSTRUCTED WITHIN THE ORIGINAL POOL SHELL. NOT SHOWING ON CURRENT GIS MAPPING BECAUSE COVERED WITH PLYWOOD BY CONTRACTOR RENOVATING EXISTING HOUSE.

7/8/2019 dking