2. Sheet E000 Note 6 (Main plan set)
This building is required to have a third party contractor conduct a two-way radio communication test in accordance with NFPA 1:11.10 and NFPA 1225 (2022 ED.) before the 105 framing inspection. St Johns County Fire Rescue’s radio control frequency is 853.8875.
If required this fire alarm will be required to monitor the BDA. The fire alarm plans would need to be revised to show the BDA and the monitoring points.
Pass this note regarding the BDA to the project manager and or BDA contractor.Whoever conducts the BDA test the following is required.
-If it passes the inspection radio testing, you will need to submit a copy of the testing results as a revision so we can record the documentation and remove the hold.
- If the third party paperwork indicates the test is not satisfactory, then the contractor will have to submit for a revision. The revision will need to include: the unsatisfactory test paperwork, outline of corrective measures, and plans to illustrate the corrective measures to meet requirements provided by the design professional.
At the final, you will be required to provide satisfactory testing by the third party contractor following the installation of the in building radio enhancement system.
Please acknowledge this requirement.
-----------------------------------
Tuesday, October 27, 2026 JLH
RTC- At this time, no BDA system has been approved or satisfactorily tested. If a BDA is ultimately required, the fire alarm plans will be revised to indicate the BDA system and associated monitoring points.