| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for creation of and office and conference room within a currently open space.. Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: Anthony Gedris 904-209-1741 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
4/9/2021
| agedris |
|
Informational
|
Visual notification will be required in the new conference room in accordance with NFPA 101-9.6.3.5.
Depending on the performance of the system a visual notification device may be required in the new office to meet the requirements of NFPA 101-9.6.3.5
|
4/9/2021
| agedris |
|
Informational
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- Fire alarm system - Fire sprinkler system
|
4/9/2021
| agedris |