Clearance Sheet N2020-004705

 Department IssuesSigned OffIntl

Plan reviewed for interior renovation of condo unit including relocation of laundry room, expanding shower, remove/replace existing doors, install doors, install a new 14'8" wall with new door, replace flooring, countertops, etc.. See affidavit for renovations and remodeling and plans for more information.

Reviewed using FFPC 6th edition effective Dec. 31, 2017. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Plans are NOT approved.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

***********************

Monday, August 31, 2020 DF: Plan review for 1st resubmittal.

Plans are APPROVED.

Reviewer: D. Feagle 904-209-1721

***********************

FIRE INSPECTOR NOTE: See comment #4 regarding the addition of Smoke Alarms (not shown on plans).

8/31/2020 dfeagle

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 6th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

8/31/2020 dfeagle

1)  Permit application only included "existing" floor plan with proposed changes clouded. No Proposed Floor Plan (with changes) provided.

Provide proposed floor plan.

Monday, August 31, 2020 DF:  Proposed floor plans provided.

8/31/2020 dfeagle

2)  Does this building/unit have a fire sprinkler system?

If yes, Provide the sprinkler head locations inside the unit to verify adequate coverage due to the changes being made.

Monday, August 31, 2020 DF: Response = NO.

8/31/2020 dfeagle

3)  Does the building /unit have a fire alarm system.

If yes, show the location of any fire alarm devices inside the unit (horns/strobes) to verify adequate coverage due to the changes being made.

Monday, August 31, 2020 DF: Response = NO.

8/31/2020 dfeagle

4)  Show on the proposed floor plan the locations of all smoke alarms / smoke detectors to verify adequate coverage due to the changes being made.

NOTE: Any smoke alarm (battery / electric type) that is more than 10 years old need to be replaced. Check the back of the smoke alarms to find the born on date or replace by date.

Monday, August 31, 2020 DF: No show a smoke alarm outside of master bedroom doors and heat detector in kitchen. NFPA 101:31.3.4.5.3 requires smoke alarms to be inside every sleeping area in accordance with 101:9.6.2.10 and as modified by 101:31.3.4.5.4.

NOTE: I spoke with Contractor Bill Lanni regarding the smoke alarms in the sleeping areas. Bill said that he agreed that smoke alarms need to be in the sleeping rooms and that he will have them installed. I told Bill that I will place in the plan review comments that the fire inspector at time of the fire final will verify the smoke alarms are installed and operational or they will not be able to give an approval for the permit fire final.

8/31/2020 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- wall and ceiling finish will meet Class A, B or C. 101:31.3.3.2.

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

8/31/2020 dfeagle