Clearance Sheet N2019-003527

 Department IssuesSigned OffIntl

Plans submitted to replace 15 rear and 35 front doors on existing condo units in an existing building.  The rear doors will be replaced on units 612,613,614,622,623,624,632,633,634,642,643,644,652,653,and 654.  The plans are rejected for the following reasons: 

--------------------------------

Plan Approved.  A full list of doors being replaced has been provided.  See approved plans.  PJW Thursday, June 27, 2019

                                                        
Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

6/27/2019 PWebb

The plans did not identify which units will have the 35 front doors replaced.  Provide this information. 

--------------

Addressed under 1st comment.  PJW Thursday, June 27, 2019

6/27/2019 PWebb

The plans do not include any cut sheets or specifications for the proposed replacements.  Provide specifications for the proposed door.  Note that the original building plans called for 1 hour doors and 1 hour frames for the front and rear unit doors.  Ensure that your plans include door specs meeting this rating.   

---------------

Included correspondence from the original architect for this project indicating that the door schedule in the plans is wrong, no rating required for the porch doors.  See attached.  PJW Thursday, June 27, 2019

6/27/2019 PWebb