Plans submitted to replace 15 rear and 35 front doors on existing condo units in an existing building.  The rear doors will be replaced on units 612,613,614,622,623,624,632,633,634,642,643,644,652,653,and 654.  The plans are rejected for the following reasons: 

                                                        
Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

The plans did not identify which units will have the 35 front doors replaced.  Provide this information. 

 

The plans do not include any cut sheets or specifications for the proposed replacements.  Provide specifications for the proposed door.  Note that the original building plans called for 1 hour doors and 1 hour frames for the front and rear unit doors.  Ensure that your plans include door specs meeting this rating.