Clearance Sheet N2017-003061

 Department IssuesSigned OffIntl

Plan reviewed with NO PENDING COMMENTS for interior renovations of 50 sf in apartment. Reviewed using FFPC 5th edition.

Reviewer: Sandra Boike 904 209 1741 
Victoria Vitori 904 209 1748
To schedule fire inspections please call 209-1740x1.

Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

6/14/2017 sboike

Make sure existing safety features are replaced and/or functional. Included but not limited to:

- smoke detectors  NFPA 101 30/31.3.4.5
- tagged (within the last year) fire extinguishers at appropriate locations  NFPA 1 13.6.
- address or unit numbers in place   NFPA 1 10.12.1
- all electrical covered  NFPA 1 11.1
***self close unit fire rated door?*** NPFA 101 30/31.3.6