Clearance Sheet M2022-007860*011

 Department IssuesSigned OffIntl

Plan reviewed for Revision to approved plans.

Revision #12 ~ Sheet #'s: CD-4.1, A1-3.2, A1-4.1, A1-4.2, A1-5.2, A1-6.1, A1-7.1, A2-1.1, A2-2.1, A2-3.1, A2-7.2, A3-1.1a, A3-1.1b, A3-1.2, A3-1.3, A3-1.4, A3-1.5, A3-2.1a, A3-2.1b, A3-2.2, A3-2.3, A3-2.4, A3-3.1, A3-3.2, A4-1.1, A4-1.1C, A4-2.1, A4-2.1C, A4-3.1, A3-4.1C, A4-4.1, A4-4.1C, A4-4.2, A4-4.2C, A5-5.3, A5-7.2, A6-4.1, A7-3.2, A8-1.1, A8-1.2, A8-2.2, A9-0.1, S1-04, S2-40,S2-40, S4-04, S7-02, P0-0.1, P1-1.1, P1-2.1, P1-3.1, P1-4.1, P3-7, P3-8, P3-9, M0-0.0, M1-1.1, M1-2.1, M1-3.1, M1-4.1, M3-7, M3-8, M3-9, M5-01, E0-00, E0-0.4, E1-1.1, E1-1.2, E1-2.1, E1-2.2, E1-3.1, E1-3.2, E1-4.1, E1-4.2, E3-1, E3-2, E3-3, E3-4, E3-5, E3-6, E3-7,E3-8, E3-9.

Revision #15 ~ Sheet #'s: E0-0.4, E1-0.0, E1-1.1, E1-1.2, E1-2.1, E1-2.2, E1-3.1, E1-3.2, E3-1, E3-2, E3-3, E4-4, E3-5, E3-6, E3-7, E3-8, E3-9.

Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

1/7/2025 dfeagle

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.

1/7/2025 dfeagle

1) One (1) set of plans for 15 Clearance Sheets (M22-7060, M22-7060*1, M22-7060*2, M22-7060*3, M22-7060*4, M22-7060*5, M22-7060*6, M22-7060*7, M22-7060*8, M22-7060*9, M22-7060*10, M22-7060*11, M22-7060*12, M22-7060*16, M22-7060*17). This comment will not be signed off until all Clearance Sheets have all of their comments addressed.

1/7/2025 dfeagle