SJC Home
Clearance Sheet M2022-007860*011

 Department IssuesSigned OffIntl

Plan reviewed for 1,958 SF Type VB(V(000)) Construction, Non-Sprinkled, Detached Storage – (Parking Garage), 5 units.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

----------------------

Wednesday, February 22, 2023 DF: Review of 1st Resubmittal.

----------------------

Wednesday, May 31, 2023 DF: Review of 2nd Resubmittal.

6/29/2023 agedris

1) I do not see emergency lighting in the storage (parking garages). 101:42.2.9, 42.8.2.9

Provide emergency lighting in these areas.

----------------------

Wednesday, February 22, 2023 DF: RTC: Emergency Lighting fixtures have been added to the parking garages. See updated sheets for more information.

Wednesday, February 22, 2023 DF: Reviewer's Response: Sheet E1-5.1 (Ancillary Buildings) has not been updated. Update Sheet E1-5.1

NOTE: No replaced "E" Sheets found in the "OLD" set of Sheets.

----------------------

Wednesday, May 31, 2023 DF: RTC: Emergency Lighting fixtures have been added to the parking garages. See updated sheets for more information.

Wednesday, May 31, 2023 DF: Reviewer's Response: Sheet E1-5.1 as of this date have not been updated to reflect emergency lighting in the garages (elevation 2/E1-5.1).

A HOLD 105 Inspection hold for revision to Sheet E1-5.1 is being placed on this permit.

5/31/2023 dfeagle

2) One (1) set of plans for fifteen (15) clearance sheets: M22-7860, M22-7860*1, M22-7860*2, M22-7860*3, M22-7860*4, M22-7860*5, M22-7860*5, M22-7860*6, M22-7860*7, M22-78690*8, M22-7860*9, M22-7860-10, M22/7860-11, M22-7860*12, M22-7860*16 & M22-78960*17.

This comment will not be signed off until ALL clearance sheets have all other comments addressed.

----------------------

Wednesday, February 22, 2023 DF: RTC: One set of plans will be provided for each of the (15) Clearance Sheets.

Wednesday, February 22, 2023 DF: Reviewer's Response: I am noting that the Plan Set contains all the building information for the 15 Clearance Sheets. Once ALL comment’s for ALL Clearance Sheets have been completed and signed off only then, can I sign this comment off.

6/29/2023 agedris

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following:  NFPA 101 7.9.2.3
(1) Failure of a public utility or other outside electrical power supply
(2) Opening of a circuit breaker or fuse
(3) Manual act(s), including accidental opening of a switch controlling normal lighting facilities.
NOTE: Our office has experienced issues with large projects that have emergency generators not being prepared to comply with item #2.

5/31/2023 dfeagle

NOTE:

If you would like to get together to go over the remaining open comments, please feel free to contact me to schedule a meeting.

My contact information is at the top of this report.

5/31/2023 dfeagle