Plan reviewed for 1,958 SF Type VB(V(000)) Construction, Non-Sprinkled, Detached Storage – (Parking Garage), 5 units.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

1) I do not see emergency lighting in the storage (parking garages). 101:42.2.9, 42.8.2.9

Provide emergency lighting in these areas.

 

2) One (1) set of plans for fifteen (15) clearance sheets: M22-7860, M22-7860*1, M22-7860*2, M22-7860*3, M22-7860*4, M22-7860*5, M22-7860*5, M22-7860*6, M22-7860*7, M22-78690*8, M22-7860*9, M22-7860-10, M22/7860-11, M22-7860*12, M22-7860*16 & M22-78960*17.

This comment will not be signed off until ALL clearance sheets have all other comments addressed.

 

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following:  NFPA 101 7.9.2.3
(1) Failure of a public utility or other outside electrical power supply
(2) Opening of a circuit breaker or fuse
(3) Manual act(s), including accidental opening of a switch controlling normal lighting facilities.
NOTE: Our office has experienced issues with large projects that have emergency generators not being prepared to comply with item #2.