Plan submitted for new 15 head above ground wet sprinkler. Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

6/29/2022 VVitori

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

6/29/2022 VVitori

1) FP0.1 is the site underground but there are no underground submittals. Are you submitting for the underground? If so provide submittals and show compliance with NFPA 24 from main to 1'aff (approx. 30').

NOTE: Underground review not completed due to not having enough information.

Wednesday, June 29, 2022 I called contact, Jeramie and asked him. He said this is above ground only. I informed him that underground permit still not pulled for this location. He asked if it will hold up aboveground permit? I said no but he needs to let GC know to get on getting the UG permitted or he wont be able to get a final.

6/29/2022 VVitori