Plan submitted for revision to 7 pages (ID.3a, ID2.0, ID8.1, E206, E300, A1.02, A8.10). Reviewed as using FFPC 8th edition effective January 1, 2024. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Reviewer: V.Vitori
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.
Page ID pages are addressing updated interior finishes. At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:
- Wall and ceiling finish in exit enclosures shall be class A. 101:30.3.3.2
- wall and ceiling finish in lobbies and corridors shall be class A or B.. 101:30.3.3.2
- Wall and ceiling finish everywhere else will meet Class A, B or C. 101:30.3.3.2.
- Floor finish in exit enclosure and exit access corridors shall be not less than Class II. 101:30.3.3.3.2
- Floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non-carpet flooring. 101:30.3.3.3.3.
If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.