Clearance Sheet M2021-009453*001

 Department IssuesSigned OffIntl

Plan submitted for access control permit. Submitted were changes made on A1.01 and A4.21 which now show locks/latches. Scope of work is to address door locking arrangements for 13 doors. Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

Wednesday, September 13, 2023 T pages revised to show what is now intended. 10 revised door locking arrangement locations.

Monday, February 26, 2024 Now only A1.02D and E300 submitted to show the exit door near clubroom no longer has card reader.
This submittal was stamped as a revision where Permit Tech accidentally let all 3 lock/latch permits out as approved. This was a "revision" to address B2 only remaining lock/latch comment.

2/26/2024 VVitori

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit. All plan pages must be the same size.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

2/26/2024 VVitori

1) 2 pages were revised (A1.01 and A4.21) to show new locks and latches that do not match what was previously reviewed and approved as part of the original building plans (T pages and review comment 9). The locking arrangement you are now showing on A1.01 and A4.21 do not match the approved technology page. If you are revising  (adding more locks, new locks, changing from what was submitted before) those locks/latches, then revise the previously submitted T pages.

NOTE: Pay attention to adding mag locks to doors in an assembly. 101:12.2.2.2.6 requires mag locks to be unlocked during the hours of operation. If any portion of the assembly building is open to the public for 24 hours, then the mag locks must not be locked for 24hours out of the day that serve the assembly portions of building. In short they would then serve no purpose if they must be unlocked 24 hours a day.

Wednesday, September 13, 2023 T pages revised to show what is now intended. 10 revised door locking arrangements. Now that I can see what is going on, review comments will begin with comment 3.

Monday, February 26, 2024 Previously signed off. I had to bring comments down which doesn't sign them off.

2/26/2024 VVitori

2) If the scope of the currently submitted revised pages only covered locks then withdraw these pages from revision so they do not conflict with approved plans.

Wednesday, September 13, 2023 T pages revised to show what is now intended. 10 revised door locking arrangements. Now that I can see what is going on, review comments will begin with comment 3.

Monday, February 26, 2024 Previously signed off. I had to bring comments down which doesn't sign them off.

2/26/2024 VVitori

9 13 23 Newly added comment based on newly provide/revised information

4) Looking at page T201, there is a card reader that was added in the corridor to that is located to bottom right of the club room. There can not be a key, tool or special knowledge to exit (this is a marked exit). 101:7.2.1.5.3

Monday, February 26, 2024 Looking at newly submitted E3-00 there is not a card reader at closest exit on 1st floor near club room. This has been removed.

2/26/2024 VVitori