SJC Home
Clearance Sheet M2021-009453*001

 Department IssuesSigned OffIntl

Plan submitted for new 440 device fire alarm system. Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

3/30/2023 VVitori

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit. All plan pages must be the same size.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

3/30/2023 VVitori

1) Unable to locate where building sprinkler backflow will be electronically supervised in accord with 101:9.7.2.1. Required by: 101:30.3.5.1 ,101:30.2.5.3.2 ,101:30.2.5.4.2 , 101:30.3.6.3.2      Show backflow is electronically supervised.

Thursday, March 30, 2023 Response to comments indicate "Changes made to pages F1, F2, F6 Marked with Clouding". bottom of fa2

3/30/2023 VVitori

2) Do not see where fire alarm will be tied in to illuminate standard lighting in corridors upon fire alarm activation due to the occupancy sensors. 101:7.8.1.2.2(5)  Also required by EOR on E-2.01 thru E2.09 note G8.   Point out how this will be achieved.

Thursday, March 30, 2023 Response to comments indicate "Changes made to pages F1, F2,  F3, F4, F5, F6 Marked with Clouding". at top of pages near NAC's

3/30/2023 VVitori

3) Do not see how visible notification is provided in the leasing office breakroom or in the business lounge. 101:9.6.3.5 Show visible notification.

Thursday, March 30, 2023 Response to comments indicate "Changes made to pages F1, F2, F6 Marked with Clouding".

3/30/2023 VVitori