1) 2 pages were revised (A1.01 and A4.21) to show new locks and latches that do not match what was previously reviewed and approved as part of the original building plans (T pages and review comment 9). The locking arrangement you are now showing on A1.01 and A4.21 do not match the approved technology page. If you are revising (adding more locks, new locks, changing from what was submitted before) those locks/latches, then revise the previously submitted T pages.
NOTE: Pay attention to adding mag locks to doors in an assembly. 101:12.2.2.2.6 requires mag locks to be unlocked during the hours of operation. If any portion of the assembly building is open to the public for 24 hours, then the mag locks must not be locked for 24hours out of the day that serve the assembly portions of building. In short they would then serve no purpose if they must be unlocked 24 hours a day.