Plans for a 1364 head fire sprinkler system for a 4 story apartment building with a clubhouse that is fire separated. The building also has a Class 1 Manual Wet standpipe system, which is a combination system with hose connections on all levels in the stairwells, and a connection on each side of the horizontal exit. The system for the apartment (residential) area is NFPA 13D, the clubhouse area is designed as NFPA 13. The building sprinkler system is supplied from the standpipe in stairs 2 and 4 on level 1. The FDC is a yard FDC that is tied into the riser above the vertical BFP. Per the building design team, the utility rooms that are indicated not to have sprinklers are for electrical/mechanical equipment, not for storage. This is permitted by 13R 6.6.6.
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.