Plan submitted for alteration to existing condo. Reviewed alteration as apartment using FFPC 7th edition effective January 1, 2021.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

12/1/2021 VVitori

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Make sure existing safety features are replaced and/or functional. Included but not limited to:

- smoke detectors  NFPA 101 30/31.3.4.5
- tagged (within the last year) fire extinguishers at appropriate locations  NFPA 1 13.6.
- address or unit numbers in place   NFPA 1 10.12.1
- all electrical covered  NFPA 1 11.1

12/1/2021 VVitori

**INFORMATIONAL ONLY NO RESPONSE NECESSARY:
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- Wall and ceiling finish will meet Class A, B or C. 101:30.3.3.2.

- Floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non-carpet flooring. 101:30.3.3.3.3.

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

12/1/2021 VVitori

Make sure new shower has grab bars in accord with 101:30.2.1.3. If you need guidance regarding the required grab bars, contact your designer.

12/1/2021 VVitori