SJC Home
Clearance Sheet M2021-008010*003

 Department IssuesSigned OffIntl

Plan reviewed for Revision of Sheets CS-1, CS-2, CS-3, A1.2, A1.3, A1.4, A2.0, A2.1, A3.0, A3.1, A3.2, A3.3, A3.4, A3.5, A10.0, A10.0b, A10.01c, A10.3, A10.4, A10.5, S1.1, S6.1, S6.2, S6.3, M4.1, E3A.1, E3A.2, E3A.3, E3B.1, E3B.2, E3B3, E3C.1, E3C.2, E3C.3, E4.1, E4.2, P1.1, P4.1 and P5.4.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

 

11) Grab Bars:

 Sheets A3.0, A3.2: Exhibit “06”, “05”:

a) Back wall grab bar is more than 8”-10” from tub rim. 24.2.8.3.2(1)

b) Back wall grab bar more than 12” from control end (shower head/valves) 24.2.8.3.2(2)

 

 Sheet A3.3: Exhibit “08”: Shower vertical bar is too low. Lower end to be between 36” and 39” AFF. 24.2.8.2.2(2)

 Sheet A3.4: Exhibit “06”: Horizontal Bar is too high. Bar is to be between 8”-10” above tub rim. 24.2.8.3.2(1)

 Sheet A3.5: Exhibit “10”: Horizontal Bar is too high. Bar is to be between 8”-10” above tub rim. 24.2.8.3.2(1)