Plan reviewed for New Fire Alarm System for New Apartment building. Full fire alarm system. FACP alarm activation, supervisory activation and trouble activation will be reported to the Clubhouse FACP which will dial out to a monitoring station. Unit types C1 and C1 HC are the designated hearing impaired units. FACP: Notifier NFW-50X

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

4/14/2022, Resubmission Reviewer: Aaron Connell 904-599-8253, aconnell@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
4/14/2022 aConnell

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications must be submitted to the Permit Center as a resubmission for the original project.

Effective 1/01/2022 you must include a written response to comments summary to clarify and illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

Resubmittals will not be approved without a response to comments.

4/14/2022, A Connell: Responses to all required comments have been submitted with the resubmittal packet as well as new plans pages.

4/14/2022 aConnell

1) Buildings 1, 2, 3 and 4’s fire alarm systems are dependent on the Clubhouse FACP for monitoring of their Alarm, Trouble and Supervisory signals, and the dialing out of these signals to a monitoring station. Buildings 1, 2, 3 and 4’s FACP permits cannot be approved until the Clubhouse fire alarm plans are approved for permitting.

4/14/2022, A Connell: All issues appear to have been addressed with the Clubhouse.

4/14/2022 aConnell

2) The Sprinkler Systems above ground control valves are required to be electronically supervised. 101:7.2.2.6.3.1(6)(a)

This includes the Fire Main Back Flow Preventer’s (BFP) control valves, the buildings sprinkler main BFP control valves, the buildings floor control valves, etc.

I did not see any inputs/leads for/to the underground building’s sprinkler line 4” BFP control valves outside the building.

4/14/2022, A Connell: Noted that the re-submitted plans now show the back-flow preventer control valves being monitored/supervised.

4/14/2022 aConnell

3) Sheet FA3.1 missing low frequency/strobe in bedroom #3 (Sheet A3.5 – construction permit plans).

4/14/2022, A Connell: Noted low frequency strobe was added and notated for Bedroom #3 on the resubmitted plans.

4/14/2022 aConnell

4) Sheet FA3.1 Fire Alarm riser identifies the hearing impaired room types as A1 HC and B1 HC. Actual rooms are C1 and C1 HC.

Adjust the fire Alarm riser’s room types to match the construction plans room types.

4/14/2022, A Connell: Noted corrections have been made  in reference to the hearing impaired rooms on sheet FA3.1 of the resubmitted plans.

4/14/2022 aConnell

INFORMATIONAL ONLY NO RESPONSE NECESSARY:

The interconnected smoke alarms in the hearing impaired units are connected via relay module and activate the strobes and the living room mini-horn/strobe in the specific unit only and transmit a trouble to the panel.

4/14/2022 aConnell