| | Department Issues | Signed Off | Intl |
|
|
1)This was a preliminary review please resubmit with approved clearance sheets for all projects associated with plans
|
| |
|
|
2) I don't see on the code summary page where the current FBC codes and NEC code are referenced also include a code analysis
|
9/30/2021
| jadams |
|
|
3)There were no MEP pages in the plan set please provide on resubmittal
|
9/30/2021
| jadams |
|
|
4) Please provide engineered structural plans using the current design criteria
NEW 9/30/21 page S1.1 shows structural design as 2015 International building code Please use the 2020 Florida Building Code Seventh edition and ASCI 7-16 for the Design criteria
|
10/11/2021
| jadams |
|
|
5) Please provide engineered floor and roof truss package 10/11/21 NEW INFORMATION HOLD WILL BE PLACED AT FRAMING INSPECTION 105 FOR EOR APPROVED TRUSS PACKAGE
|
10/11/2021
| jadams |
|
|
6) Please provide current energy conservation form ( energy sheets)
NEW 09/30/21(need complete set Interior lighting compliance and mechanical compliance certificate )
|
10/11/2021
| jadams |
|
|
7) Please address all of Fire Service comments
|
| |