SJC Home
Clearance Sheet M2021-008010*001

 Department IssuesSigned OffIntl

1)This was a preliminary review please resubmit with approved clearance sheets for all projects associated with plans

 

2) I don't see on the code summary page where the current FBC codes and NEC code are referenced also include  a code analysis

9/30/2021 jadams

3)There were no MEP pages in the plan set please provide on resubmittal

9/30/2021 jadams

4) Please provide engineered structural plans using the current design criteria

NEW 9/30/21 page S1.1 shows structural design as 2015 International building code Please use the 2020 Florida Building Code Seventh edition and ASCI 7-16 for the Design criteria

 

5) Please provide engineered floor and roof truss package  

 

6) Please provide current energy conservation form ( energy sheets)

NEW 09/30/21(need complete set Interior lighting compliance and mechanical compliance certificate )

 

7) Please address all of Fire Service comments