Clearance Sheet M2021-006999

 Department IssuesSigned OffIntl

Plans for the installation of a Generac SD300, 300KW diesel life safety generator.  The generator is fed by a 1500 gallon double wall tank that is located outside of the building, permitted separately. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

8/4/2022 PWebb

INFORMATION ONLY, NO RESPONSE NECESSARY

Generators for ALF’s and Nursing homes are required to have 72-96 hours of fuel on site per Florida Administrative Code 59A-36.025 and 59A-4.1265.   The Generac SD300 generator provided burns 22.1 gallons per hour. With the 1500 gallon tank provided it will run for 67 hours at 100%.  Please note that the enforcing agency may require you to upgrade the size of your tank to meet this requirement. 

 

8/4/2022 PWebb