SJC Home
Clearance Sheet M2021-006791

 Department IssuesSigned OffIntl

Plan reviewed for new NFPA 13R Sprinkler system for a tri-plex (3 family structure).

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

 

1) Plans include sheet 1 of 3 which does not appear to provide data for this building. If this is correct please remove the sheet from the submittal or, point out the data on sheet 1 of 3 that is a part of this system review.

 

2) The spec sheets show two different residential manifold manufacturers with multiple manifold types each. Which manifold manufacturer and manifold model will you be using? If you have not determined which manufacturer you will be using as of yet, please identify which model of each manufacturer you would be using.

 

3) The Garages Do not have sprinklers. 13R:7.3.3, 7.3.3.1

Provide sprinklers in the garages.

 

4) The Covered Lanai’s Do not have sprinklers. The building construction type is V (VB). 13R:6.6.5, 6.6.5.1

Provide sprinklers in the cover Lanais.

 

5) Provide the manufacturer’s spec sheet for the FDC.

 

6) I do not see the spec sheet for the three-way valve and gauge on supply side of the manifold.