SJC Home
Clearance Sheet M2021-004518

 Department IssuesSigned OffIntl

Plans for a 30 head Wet NFPA 13D sprinkler system for a duplex for the aboveground only.  The attic piping will be insulated to provide the freeze protection.  No FD connection required. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

 

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

 

1) The common sprinkler riser is currently shown in one of the private units garage.   A common sprinkler riser cannot be located within a private unit.  When you relocate it, ensure that it is protected from freezing and indicate how.