1) The plans have a note that indicates that the FACP, the smoke detector, the pull station and the horn strobe "locations to be determined by the AHJ." There is no building layout indicating where the devices will be located. Provide a floor plan indicating where the devices will be located. We will then review your proposed layout.
--------------------------
Wednesday, September 7, 2022 PJW- Plans were submitted showing the FACP and devices located inside the private garage of one of the units. The FACP cannot be located within someone's private unit. Relocate the panel and devices to a location that is not controlled by a unit owner/tenant.
----------------------------
Wednesday, September 7, 2022 PJW- Supervisor Gedris spoke to a project contact and it was agreed upon that the FACP will be located in the NEMA enclosure on the exterior wall of the garage. A rendering was emailed to him, printed and attached to the plans. The Smoke and the pull will be located in the NEMA enclosure.