SJC Home
Clearance Sheet M2021-004511

 Department IssuesSigned OffIntl

Plans for a 5 device fire alarm system for a triplex intended only to monitor the fire sprinkler system. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

9/7/2022 PWebb

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

9/7/2022 PWebb

1) The plans have a note that indicates that the FACP, the smoke detector, the pull station and the horn strobe "locations to be determined by the AHJ."  There is no building layout indicating where the devices will be located.  Provide a floor plan indicating where the devices will be located.  We will then review your proposed layout. 

--------------------------

Wednesday, September 7, 2022 PJW- Plans were submitted showing the FACP and devices located inside the private garage of one of the units.  The FACP cannot be located within someone's private unit.  Relocate the panel and devices to a location that is not controlled by a unit owner/tenant. 

----------------------------

Wednesday, September 7, 2022 PJW- Supervisor Gedris spoke to a project contact and it was agreed upon that the FACP will be located in the NEMA enclosure on the exterior wall of the garage.  A rendering was emailed to him, printed and attached to the plans.  The Smoke and the pull will be located in the NEMA enclosure. 

9/7/2022 PWebb