Clearance Sheet M2021-004511

 Department IssuesSigned OffIntl

Plans for a 6997sf 3 unit apartment building (triplex) that was reviewed using the apartments chapter.  


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

This building is required to be protected with fire sprinklers. NFPA 101:30.3.5.1.   Indicate this on the building code summary and provide the fire sprinkler engineers criteria (FP page(s)), indicated below. 

 

An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided.  It is not a full set of shop drawing  FLORIDA ADMINISTRATIVE CODE 61G15-32.004

 

3) Provide grab bar details for bathtubs and showers in accordance with 30.2.1.3 and 24.2.8 of NFPA 101.