2) The permit package has been submitted to provide a BDA system for the clubhouse only. However the plans submitted show the BDA install for all buildings, even those that have not been submitted to our office for review/permit (Flats 3, Flats 4, ALF, and Memory Care).
Our office cannot review only the antennae arrangement for the clubhouse, because the antennae cannot function alone. At a minimum to approve the clubhouse BDA, Flats 1 would need to be submitted with it.
Action: 1)Provide an application for each building that is included in the scope of the review at this time. At a minimum for the clubhouse review you would need an application for the clubhouse and Flats 1, with the associated plans.
2) Remove the plans from the set that reference any of the other buildings that are not part of the scope of this review. At a minimum, place a prominent note on the sheets that are not applicable indicating to some affect that the sheet is not part of this review and will be submitted separately.
You can submit plans/applications for as many buildings as you wish currently that have building permits. Flats 3, Flats 4, The ALF, and Memory Care must not be submitted for review until after building plans are approved and a permit issued.
--------------------------------
Thursday, August 18, 2022 PJW- Plans and applications submitted for clubhouse and flats 1 only.
Thursday, August 18, 2022