Plans for a revision to the previously approved plans for sheet A001, A102, A402, A405, A502, E302, E402, E702 and M302.  The revision is mostly the changing from the entire corridor on the second floor being a smoke partition to meet NFPA 101:8.6.6 to only providing a smoke partition directly around the opening to include the use of an electronic smoke curtain.   Specifications have been provided for the curtain that will be tied into the fire alarm system. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.