Plans for a revision to the previously approved fire sprinkler plans to remove some dry sprinkler heads that were located in non combustible voids. The removal is permitted by NFPA 13:8.15.1.2.1. The removal also appears to meet the allowance of NFPA 13:8.15.1.2.2.
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.