SJC Home
Clearance Sheet M2021-004310

 Department IssuesSigned OffIntl

Plans for a BDA system for Flats 2, which consists of installing a BDA remote unit with associated indoor antennae which are part of a campus wide BDA system.  The Yagi antennae and main BDA panel are located in Flats 1. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

 

1) The address on the plans is 300 Birnam Oak which is Flats 1.  Flats 2 is 250 Birnam Oak. 

 

2) Per our radio system license holder, the maximum propagation delay acceptable is 5 microseconds.   The plans indicate 3.5-6.5 microseconds delay on sheet 1 of 18.  NFPA 1225:18.8.2. 

 

3) All repeaters, transmitters, receivers, signal booster components, remote annunciators and operational consoles, power supplies, and battery charging system components, must be listed and labeled per UL2524.

I do not see this listing for the DAS indicated on the plans.   The battery backup system does have this listing.  Demonstrate any applicable components listed above have this listing.   

 

4) Informational comment, not response necessary.   

NFPA 1225 references DAQ for signal strength requirements not minimum DBM as NFPA 1221 does.   Please address this in future submittals.  I will move forward with this submittal as indicated by DBM.