Clearance Sheet M2021-004308

 Department IssuesSigned OffIntl

Plan for the installation of radio enhancement system (BDA) components for Flats 1 which is part of a complex wide, interconnected BDA System.    The complex-wide system is designed as follows: The Master unit and the roof mounted Yagi antennae will be installed in Flats 1, which will provide signal for Flats 1 and the clubhouse.  Remote unit 1 will be installed in Flats 2 and will provide signal for flats 2 and flats 3.   Remote unit 2 will be installed in Flats 4 and only provide signal for flats 4.  Remove unit 3 will be installed in the ALF building and will provide signal for the ALF and Memory Care buildings.  The remote units are connected to the master unit by dedicated underground fiber.    

SmartGuard 1/2 Armored coaxial cable will be used in the buildings which meet level 1 surviability.  Splitters will be in J boxes to maintain the survivability.   


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020. Reviewed to NFPA 1225
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

8/18/2022 PWebb