Plan submitted for revision to 6 pages (A0, A0.01, A2.01, A8.20, A8.21, E4.30). Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

 

7/28/2023 VVitori

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 7th Ed.

7/28/2023 VVitori

1) Double doors 114 are showing they are removed in this revision submittal. Exiting pages A1.02D and A4.32 show the corridor wall to both "open to below" and "cardio" as a 1hour separation. Explain or point out how the opening where door 114 is now being protected. 101:8.3.3

Thursday, July 27, 2023 Looking at the newly submitted A8.20 page I do not see (In these revised pages nor existing approved scanned in pages) where the wall that separates the corridor from cardio is fire rated to maintain exit access corridor fire rating. 101:30.3.6

I showed Supervisor Gedris and he called his contact for this project and said I will hold plan in my office until Monday July 31, 2023 looking for something to show that the wall maintains the fire rating.

Friday, July 28, 2023 New plan page A8.20 dropped off showing this wall is now 1 hour fire rated.

7/28/2023 VVitori