Plan submitted for separate fire alarm permit to monitor fire alarm via starlink cellular communicator. Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Reviewer: V.Vitori For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us. To schedule fire inspections call 827 6842 (automated system). Questions about inspections or resubmitting your plans call 209 1740x1.
|
6/30/2023
| VVitori |
|
|
Pursuant to NFPA 101-30.3.4.3.2 Annunciation and Annunciation Zoning in accordance with 9.6.7 shall be provided unless the building complies with 30.3.4.3.3 (2 or less floors and 50 or less units) or 30.3.4.3.4 (4 or less floors and 16 or fewer units and Fully Sprinklered). The Sprinkler System Shall be permitted to be annunciated as a single zone in accordance with 9.6.7.4.5 and 9.6.7.4.6. Trouble and Supervisory shall be audible and visual in accordance with NFPA 72. Where the system serves more than one building EACH building shall be annunciated separately in accordance with 9.6.7.7 ADDITIONALY- in accordance with NFPA 72 – 26.2.1.3 signals received by zone shall be transmitted to dispatch by zone and 26.2.1.4 signals received by point ID shall be transmitted to dispatch by point ID.
|
6/30/2023
| VVitori |