Plan submitted for revision to 13 pages (A0.00, A0.01, A4.37, E301, E302, E303, E304, E305, E306, E414, E424, E434, E450, E452). Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

11/29/2022 VVitori

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

11/29/2022 VVitori

1) Page E450 shows 3 exit signs removed (2 in clubroom and another in corridor in front of restrooms). This leaves no visible exit signs from the clubroom or corridor. 101:7.10.2.1  Provide exit signs or provide code based justification for removal of previous exit signage.

Tuesday, November 29, 2022 Response to comments from Humphreys and Partners indicate "The three exit signs indicated in your comment ere incorrectly removed in the prior E-4.50 sheet submittal. In an effort to coordinate the Electrical Plan with the previously submitted Egress Sheet A-1.02E, it was found that Egress through the swimming pool deck was incorrectly or unclearly  indicated on both sheets. The intent of the egress plan is to direct occupants to the front of the clubroom corridor and then to either the stairwell egress point to the east and the mail room entry point on the south. We have corrected Egress Plan Sheet A-1.02E to remove the errant "EXIT" note at the door from the restroom corridor. We have also clarified the exit signs on Sheet E-4.50 to reflect the intended egress travel path to match those indicated on the original egress plan. Please refer to annotated Sheet A-1.02E, included also as Exhibit A to this response letter. PLEASE ALSO NOTE: An updated Sheet Index - Sheet A-0.01 has been included with this resubmittal to reflect the inclusion of Revised Sheet A-1.02D as part of the overall REV 15 submittal."

11/29/2022 VVitori