Clearance Sheet M2021-002204

 Department IssuesSigned OffIntl

Plan submitted for revision to 59 pages (A0.00, A0.01, A1.01, A1.01, A1.05a, A2.02, A4.14, A4.15, A4.16, A4.24, A4.25, A4.26, A4.35, A4.36, A4.37, A5.10, A5.13, A6.11, A6.11a, A6.12, A6.12a, A6.13a, A6.13, A6.14, A6.14a, A8.07, A8.10, A8.20, A8.30, A8.40, S1.01, S1.04, S2.12, S2.13, S2.14, S2.15, S2.21, S2.22, S2.25, S2.31, S2.32, S2.33, S2.34, S2.35, S2.41, S2.51, S2.61, S2.81, S3.01, S3.02, S3.03, S4.09, S4.10, S4.11, S4.12, E101, E460, E470, E608). Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

6/13/2022 VVitori

1) Only 1 copy of plans submitted. You must submit 2 copies. One will be stamped office (which will be retained here) and the other will be job copy (to be kept on site).

Monday, June 13, 2022 Response to comments indicate "Owner is delivering two complete copies of REV 12 along with addition of Sheet A-1.02E"

6/10/2022 VVitori

2) Page A2.02 now only has 1 means of egress off the 2nd floor deck again (see original comment 8 from original plan review.) This update indicates what was the 2nd exit off the deck (back through interior of building) now requires the use of a key fob from exterior deck area to interior. Show 2 exits from 2nd floor deck area that comply with 101:7.  101:12.2.4  101:7.2.1.5

NOTE: Deck occ load 78 and travel distance from deck only 115+'.

Monday, June 13, 2022 Response to comments indicate that the designer had reduced the deck occupant load via planter boxes to get the occupant load to 49p which allowed him 1 exit off the deck.

6/13/2022 VVitori

3) New gas fire place shown on A8.10 and A8.40. Is gas provided from piped utility or new on site tank? If tank and over 60gal you will need to provide documentation showing compliance with respective fuel code via deferred permit application.

Monday, June 13, 2022 Response to comments indicate "The project owner has indicated that the lower deck amenity fireplace will connect to the metered TECO gas lines provided to Building 1 and amenity deck area."

6/13/2022 VVitori