Clearance Sheet M2021-002204

 Department IssuesSigned OffIntl

Plan submitted for revision to 59 pages (A0.00, A0.01, A1.01, A1.01, A1.05a, A2.02, A4.14, A4.15, A4.16, A4.24, A4.25, A4.26, A4.35, A4.36, A4.37, A5.10, A5.13, A6.11, A6.11a, A6.12, A6.12a, A6.13a, A6.13, A6.14, A6.14a, A8.07, A8.10, A8.20, A8.30, A8.40, S1.01, S1.04, S2.12, S2.13, S2.14, S2.15, S2.21, S2.22, S2.25, S2.31, S2.32, S2.33, S2.34, S2.35, S2.41, S2.51, S2.61, S2.81, S3.01, S3.02, S3.03, S4.09, S4.10, S4.11, S4.12, E101, E460, E470, E608). Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

 

1) Only 1 copy of plans submitted. You must submit 2 copies. One will be stamped office (which will be retained here) and the other will be job copy (to be kept on site).

 

2) Page A2.02 now only has 1 means of egress off the 2nd floor deck again (see original comment 8 from original plan review.) This update indicates what was the 2nd exit off the deck (back through interior of building) now requires the use of a key fob from exterior deck area to interior. Show 2 exits from 2nd floor deck area that comply with 101:7.  101:12.2.4  101:7.2.1.5

NOTE: Deck occ load 78 and travel distance from deck only 115+'.

 

3) New gas fire place shown on A8.10 and A8.40. Is gas provided from piped utility or new on site tank? If tank and over 60gal you will need to provide documentation showing compliance with respective fuel code via deferred permit application.