SJC Home
Clearance Sheet M2021-002204

 Department IssuesSigned OffIntl

Plan submitted for Building 1 (type III layout) which is a 85270sf, 4 story, fire sprinklered , construction type VA, mixed use: apartment, business, assembly building. Reviewed as mixed apartment, assembly and business using FFPC 7th edition effective January 1, 2021.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

 

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

 

1) Page A-1.02a shows plans were designed using FFPC 6th edition. Update references used for design. FAC 69a-60

Tuesday, May 18, 2021 Page A-1.02a updated.

5/18/2021 VVitori

2) Looking at page A-1.03, grab bars are not provided in accord with 101:30.2.1.3.

Tuesday, May 18, 2021 A-1.03 updated.

5/18/2021 VVitori

3) Do not see where/ how fire riser will be kept above freezing.

Tuesday, May 18, 2021 Response to comments dated April 23, 2021 indicates "Mechanical indicate an Electric Wall Heater in the riser room. Please refer to previously submitted Sheet H4.30, and also to response prepared by Electrical Engineer of Record - Migre Engineers included with this response package."

Shown on H4.30 and H601

5/19/2021 VVitori

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until a permit has been pulled :

- Fire alarm system (PIV tamper req page F101 sprinkler DC and several trade offs, tie some fire smoke dampers H606 and E420, voice evac 101:12.3.4.3.6
- Fire sprinkler system (13, attic protected, dry pipe under exterior deck)
- Fire underground
- Wet class I standpipe
- BDA In Building Radio System at 105 framing.

5/19/2021 VVitori

4) Point out sample stairway identification in accord with 101:7.2.2.5.4.

Tuesday, May 18, 2021 Response to comments dated April 23, 2021 indicates "We have revised Sheet A-600 to include sample stairway identification signage per FFPC 101:7.2.2.5.4".

5/19/2021 VVitori

5) Occupant load of each 1st and 2nd floor is over 100 people. Looking at A-2.01 I do not see where exit doors will receive either panic or fire exit hardware. 101:12.2.2.2.3  

Tuesday, May 18, 2021 Response to comments dated April 23, 2021 indicates "We have revised Sheet A-1.02E to more clearly identify Egress Path and Egress discharge pointed along with and anticipated occupant loads. Regarding Exit Devices, we have updated the Storefront Schedule to indicate panic hardware for all required doors."

5/19/2021 VVitori

6)  Will door between "open lobby" to "open clubroom" be locked against egress?    101:7.2.1.5

NOTE: Unable to locate door numbers on A4.31 for multiple doors but specifically door mentioned above.

Tuesday, May 18, 2021 Response to comments dated April 23, 2021 indicates "The doors to the Lobby/Leasing area will be locked after hours. We have revised Sheet A-1.02E to indicate the revised Egress Path and Egress discharge points from the Clubroom spaces."

E450 has an exit sign going from clubroom to lobby/leasing.

 

7) Where is the main entrance/exit for the clubhouse and fitness room? Show the occupant load of this space will meet 101:12.2.3.6.3.

Tuesday, May 18, 2021 Response to comments dated April 23, 2021 indicates "We have revised and clarified the entry and exit for the Clubhouse and Fitness Room spaces. Occupant Loading for all amenity spaces, based upon both the FBC and FFPC are indicated on both the Code Summary Sheet A-1.02a the Occupancy and Egress Sheet A-1.02E."

Exit locations on A-1.02e do not match the exit signage provided on E450 and E451.

 

8) Where are the 2 means of egress for the 2nd floor deck? 101:12.2.4  101:7.2.1.5

Tuesday, May 18, 2021 Response to comments dated April 23, 2021 indicates "The 2 Means of Egress Paths from the 2nd FLR deck is: (1) Direct access to an Exterior Stair to Grade and (2) Access through the adjoining work share space to an enclosed Exit Stairwell. Please refer to revised Sheet A-1.02E for an indication and travel path distance for these two exit paths."

Looking at page A8.20 and A2.02, it shows the exterior door requires the use of a key fob to egress going from exterior 2nd fl deck towards the enclosed exit stairwell. This door can not be locked against egress. Also E451 shows no exit sign on the exterior going in. 

 

9) Bottom right of A2.01 indicates requirements for doors with access controlled egress (now known as sensor release of electrical locking system). Which doors are getting sensor release of electrical locking system controlled egress? Make sure they comply with 101:12.2.2.2.6 also.

Tuesday, May 18, 2021 Response to comments dated April 23, 2021 indicates "Please refer to Sheet A-2.02 (right side) for a detailed Storefront Door hardware schedule. The schedule is keyed to the specific door locations and indicates which have release mechanism per 101:7.2.1.6.2. Descriptions in the hardware schedule have also been supplemented."

Now seeing door locations with the sensor release, how will they comply with 101:12.2.2.2.6? How will the sensors to be turned off anytime the assembly is occupied? Also do not see where all sensor release doors will have emergency lighting in the vicinity.

NOTE: doors with hardware 7, 8, 9 ,and door SF-4, on page A201and A202

 

10) Will fans in fitness room be considered HVLS fans?  NFPA 13:11.1.7

Tuesday, May 18, 2021 Response to comments dated April 23, 2021 indicates "No. Fitness Room fans will NOT be an HVLS type fan."

5/18/2021 VVitori

11) Looking at page A4.31- A4.36, A8.10, and A2.01 unable to locate where several fire or smoke doors will be provided with self closing or automatic closing hardware. 101:8.3.3.3.5   101:8.4.3.5   101:30.3.6.2.3  101:8.6.9.1

NOTE: Do not forget smoke separation and of : a) doors that open on to exit access corridors (including elec room and mechanical) and b) storage rooms outside of dwelling units, c) fitness room doors to corridor. 101:30.3.2.1.1

Tuesday, May 18, 2021 Response to comments dated April 23, 2021 indicates "We have revised and clarified the Door Hardware Schedule and Hardware Set assignment on sheet A-2.01. Hardware Sets have been updated to include both automatic closing hardware, panic devices, and smoke control seals."

Make sure all door hardware on fire rated doors are fire rated. 

5/19/2021 VVitori

**INFORMATIONAL ONLY NO RESPONSE NECESSARY:
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- wall and ceiling finish in exit enclosure will meet class A.

- wall and ceiling finish in lobbies and corridors will meet class A or B.

- Wall and ceiling finish will meet Class A, B or C. 101:30.3.3.2.   101:12.3.3.

- floor finish in exit enclosures and corridor shall be not less than class II.

- Floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non-carpet flooring. 101:30.3.3.3   101:12.3.3.5

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

5/19/2021 VVitori

This building is required to have a third party contractor conduct a two-way radio communication test in accordance with NFPA 1:11.10 and NFPA 1221 (2016 ED.) prior to the 105 framing inspection. 

-If it passes the inspection radio testing at the framing stage, you will need to submit this information as a revision so the hold maybe removed. 

- If the third party paperwork indicates the test is not satisfactory, to have hold removed you will need to submit : the unsatisfactory test paperwork, outline of corrective measures, and plans to illustrate the corrective measures to meet requirements provided by the design professional.  Then at the final, you will be required to provide satisfactory testing by the third party contractor following the installation of the in building radio enhancement system.

St Johns County Fire Rescue’s radio control frequency is 853.8875.

5/19/2021 VVitori

The required in building radio system requires lightening protection. Systems shall have lightening protection that complies with NFPA 780. At this time the fire department will not review or inspect this type of system. This office requires a 3rd party inspection. The installing contractor will be required to provide certification documentation to the fire inspector at the time of fire final indicating the lightening protection is in compliance with NFPA 780 and UL96A.

5/19/2021 VVitori

12) Point out where exit access corridor doors (room doors, mechanical, storage) are at least 20 min rated doors. 101:30.3.6.2

Tuesday, May 18, 2021 Response to comments dated April 23, 2021 indicates "Please refer to updated and revised Sheet A-2.01 Door Schedule for a corrected Door Rating indication. Schedule has been updated to provide ratings as follows:

Unit Entry  20min

Mech/Elec Rm 45min

Storage Closet Doors 45min

Garage Access Doors 45 min

Trash Rm Access Doors 45min "

5/19/2021 VVitori