3) Where are the fire pump audible and visible signals located (at a point of constant attendance)? 20:10.4.7
Tuesday, July 12, 2022 Response to comments indicate "A weather proof audio/visual device has been provided by the fire alarm sub-contractor and is shown on the fire alarm drawings. Horn/strobe has been clarified on the fire pump drawing."
A device outside is not considered a constantly attended location. And this maintenance building is not showing that it will receive a fire alarm. Do they intend to put a fire alarm in this structure?
Tuesday, July 12, 2022 12:58:57 PM I called sprinkler contact and was transferred to someone's voicemail. I stated I do not see a fire alarm going in this building but this structure am being told this structure will have a horn strobe. I asked is this building going to get a fire alarm or will it be tied into another building (which none of those fire alarms have been turned in yet)?
Thursday, July 14, 2022 Sometime this morning I spoke with Ed Snider (EOR) that he cant control if a fire alarm goes here or not. He just informed there was to be a horn strobe as that is what he saw the building plans reference. This is up to the architect to coordinate. I said I will just add a hold to one of the buildings that will have a fire alarm to remind me to look for this.
After I hung up with Mr. Snider, I looked at main building plans. Top left of E460 indicates "monitor fire pump and switches from building 5 fire alarm system". I added a note to the fire alarm hold to see fire alarm hold comment in approved building comments.