Clearance Sheet M2021-002204*004

 Department IssuesSigned OffIntl

Plan submitted for revision to 2 pages (FA2 and FA3). Scope of revision is to relocate panel due to lack of installation space. Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

9/15/2023 VVitori

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 7th Ed.

9/15/2023 VVitori

1) I am unable to locate where the new FACP is going. I do see a new box labeled "...….." that is bubbled on the 2nd floor across from the NAC. Confirm this is where the FACP is going.

NOTE: If the FACP is no longer within 10' of entrance/exit, an annunciator will need to be added within 10' of the entrance/exit. 101:9.6.6

Friday, September 15, 2023 It was pointed out through email that the annunciator is labeled as "RAN". I called and Mr. Hollins confirmed that the "...….." on the 2nd floor is where the FACP is going.

9/15/2023 VVitori