SJC Home
Clearance Sheet M2021-002204*004

 Department IssuesSigned OffIntl

Joe Maguire Coastal Utilities 904-384-2419

This review covers the underground fire main for 6 private FHs and 7 buildings (6 (4 story) apts and maintenance bldg.)

Plan APPROVED for private fire main beginning at 8" RPDA BFP to be freeze protected to a (fire pump-installed by others-separate permit) inside pump house and back out to 8" DR-18 to supply 6 private fire hydrants around the complex and supply 6 apartments with 6" PIVs and 6" fire sprinkler risers to finish 1 ft above finish floor. (2470 feet +/- 8" DR-18 and 290 feet +/- 6" DR-18)

***NOTE TO FIRE PLAN REVIEWER FOR ABOVEGROUND SPRINKLER: FDCs on buildings and check valves required at bottom of fire risers.***

***HOLD 109 placed on maintenance building for fire pump permit.***

12/30/2021 SMurray