4) Do not see where visible signals provided throughout. 101:9.6.3.5 101:30.3.4.3.1
Tuesday, March 21, 2023 Response to comments indicate "No units are allocated for hearing impaired on the ADA Matrix."
Either : a) Provide documentation from Building Owner/Property Management Company that they will a1) not allow hearing impaired residents to occupy the structure(s), a2) not allow hearing impaired guests in the structure(s) and 3a) each of the structures will need to be posted with signage at each entrance indicating no hearing impaired residents or guests allowed. OR
b) provide visible notification throughout.
4) Do not see where visible signals provided throughout. 101:9.6.3.5
Tuesday, March 21, 2023 Response to comments indicate "No units are allocated for hearing impaired on the ADA Matrix."
Either : a) Provide documentation from Building Owner/Property Management Company that they will a1) not allow hearing impaired residents to occupy the structure(s), a2) not allow hearing impaired guests in the structure(s) and 3a) each of the structures will need to be posted with signage at each entrance indicating no hearing impaired residents or guests allowed. OR
b) provide visible notification throughout.
Tuesday, March 28, 2023 Received email from designer Martin Koch dated 3/24/23 at 1226 in short indicating they meet the exception of 101:30.3.4.3.1(1). The email goes on to say the owner can accommodate a unit for a hearing impaired resident. Email printed and turned in to be scanned.