SJC Home
Clearance Sheet M2021-002204*003

 Department IssuesSigned OffIntl

Plan submitted for wet 801 head nfpa 13r sprinkler system  (CPVC pipe - FlameGuard) with on building fdc and manual class I wet stand pipes (steel pipe) in each stair. Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

NOTE: Monday, June 6, 2022 11:10:39 AM I called and was able to speak with Mr. Snyder. He confirmed that the standpipes are separate from the sprinkler system.

Unable to locate hose connection provided on the roof. 14:7.3.2.9 Roof slope shown on FPD.1 is 5 in 12.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

 

1) Looking back at my building notes this building is 78000+ sf. I see that the stand alone stand pipes and sprinkler piping branch off the main bulk riser. Then looking at sprinkler piping for floors 1-4 (pages FP1.1-FP1.4) I do NOT see how the sprinkler is broken in to separate systems either by floor or so that it serves less than 52000sf. 13r:6.1.1  Show how the 13r sprinkler system does not cover more than 52000sf.

Wednesday, July 13, 2022 Response to comments indicate "See NFPA 13r handbook discussing the intent of section 6.1". Below this response was 13r:6.1. Essentially the 52000sf limitation is per floor. The over all building SF is 78000sf.

7/13/2022 VVitori

2) Plans show SIN R3516 head with k factor 4.9 being used. Manufacturer spec sheet page 3 for this SIN shows max coverage area of 16 x 16. How is this head being used in many locations that appear to exceed the 16x16 max coverage area. Example of SOME spaces: 20 x 20 bedrooms, living room areas in 2 bdrm on corners of building, corridor heads are located 18' apart. 13r:6.4.6.3

Wednesday, July 13, 2022 Response to comments indicate "Reliable 4.9k pendant is listed for up to 20x20 spacing. The sprinkler spacing is defined as 18x18 unless noted otherwise. You may be looking at the 3.0k pendent on page 3 of the cut sheet which the spacing is limited to 16x16 spacing."

7/13/2022 VVitori

3) Page FPD.2 shows detail for antifreeze. Confirm this is a standard detail and that this isn't being used in this system. If antifreeze being used in this building, point out where antifreeze will be used.

Wednesday, July 13, 2022 Response to comments indicate "Only building 1 has the antifreeze system. This sheet is updated to state this detail applies only to building 1."

7/13/2022 VVitori

Insulation must be installed prior to sprinkler final. 13r:6.7.2

7/13/2022 VVitori

4) I am confused looking at typical floor control detail (stand pipe) on upper left of FPD.1, it shows a stand pipe with a connection above the hose connection looks like what would goto supply floor sprinklers (for a combined standpipe). Upper mid page of FPD.1 also shows building elevation detailing the stand pipe for buildings 1- 3. But page FP1.0 shows the stand pipes are not combined with the sprinklers. Looking at piping the bulk main splits and feeds the stand pipes and then the sprinklers separately.

Either: a) update all images showing this is a combined standpipe/sprinkler OR b) update all images to show this is NOT a combined standpipe/sprinkler.

Wednesday, July 13, 2022 Response to comments indicate "Detail regarding the floor control assembly has been removed."

7/13/2022 VVitori

5)  Unable to locate gauges at main drain connection and top of each stand pipe. 14:5.5.1

NOTE: I will then be looking for shut off valve and drain at each gauge. 14:5.5.1.2

Wednesday, July 13, 2022 Response to comments indicate "Pressure gauge is located at the top of each standpipe. Please see the standpipe cross sections shown in the details sheet."

I am still not seeing the gauges, shut off valve and drain at the top of each stand pipe. What page number? Where? At the top of FPD.1 there is small blurred print at the top of the stand pipes that is illegible. Is this what you mean? What does it say?

 

6) Where are the isolation valves for each stand pipe? 14:6.3.2

Wednesday, July 13, 2022 Response to comments indicate "Isolation valves are shown on the bulk standpipe layout sheet. Also each isolation valve is labeled in the keynotes section of the drawing." 

I found it on FP2.0 Keynote 4.

7/13/2022 VVitori

Reminder for buildings under construction NFPA 14 Ch12 :  

-At least one approved hose valve for attaching fire department hose shall be provided at each intermediate landing or floor level in the exit stairway, as determined by the authority having jurisdiction. 14:12.5.1

The standpipes shall be extended up with each floor and shall be securely capped at the top. Top hose outlets shall be not more than one floor below the highest forms, staging, and similar combustibles at all times. 14:12.6

7/13/2022 VVitori

7) 1 set of plans for 3 separate sprinkler permits under master permit 12201284, 12201285, 12201286. This comment will not be signed off until both clearance sheets have all other comments addressed.

 

8) Unable to locate FDC specifics. FDC connections on piping LARGER than 2 inches shall be equipped with a five (5) inch Storz connection and shall have a 30 degree downward deflection. NFPA 24:5.9.1.2, and 5.9.2.4

Wednesday, July 13, 2022 Response to comments indicate "details sheet showing the fdc has been updated to note the 30 degree 5"storz connection."

7/13/2022 VVitori