SJC Home
Clearance Sheet M2021-002204*002

 Department IssuesSigned OffIntl

Plan submitted for new 216 device monitored fire alarm system. Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

 

1) Do not see where all valves (including backflow and PIVs) are electronically supervised in accord with 101:9.7.2.1.1. Req by 101:30.3.5.1, sprinkler design criteria on F101, fire alarm design criteria E606, and several trade offs utilized. Show backflow/PIVs are electronically supervised.

Tuesday, March 21, 2023 Response to comments indicate Change made to FA2 marked with clouding.

3/21/2023 VVitori

2) Looking at E601 (FSD), the EOR wanted the damper smokes to be tied into fire alarm and fire alarm to shut dampers. According to E410-E413 there are a handful of dampers per floor. Looking at the shop drawings I see no dampers or smokes for each of the dampers.

NOTE: These smokes should not activate alarm but supervisory only. 101:9.6.3.2.2.

Tuesday, March 21, 2023 Response to comments indicate Change made to FA2, FA3, FA4, FA5, FA6, FA7 marked with clouding.

3/21/2023 VVitori

3) Page 6 shows that smokes will activate alarm. We do not want smokes that close the doors, dampers or elevator recall/shutdown to activate the alarm, just supervisory. 101:9.6.3.2

Tuesday, March 21, 2023 Response to comments indicate Change made to FA6 marked with clouding.

3/21/2023 VVitori

4) Do not see where visible signals provided throughout. 101:9.6.3.5  101:30.3.4.3.1

Tuesday, March 21, 2023 Response to comments indicate "No units are allocated for hearing impaired on the ADA Matrix."

Either : a) Provide documentation from Building Owner/Property Management Company that they will a1) not allow hearing impaired residents to occupy the structure(s), a2) not allow hearing impaired guests in the structure(s) and 3a) each of the structures will need to be posted with signage at each entrance indicating no hearing impaired residents or guests allowed.    OR

b) provide visible notification throughout.

 

5) FACP is not within 10' of main door.  Show annunciator within 10' of entrance door. 101:9.6.6.

Tuesday, March 21, 2023 Response to comments indicate Change made to FA1, FA5, FA6 marked with clouding.

3/21/2023 VVitori