SJC Home
Clearance Sheet M2021-002204*001

 Department IssuesSigned OffIntl

Plan submitted for access control for Buildings #1 through 6. Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

Monday, June 5, 2023 Plan submitted is for access control for buildings 1-7. The building locking arrangements are provided with mechanical release or electric strikes. There is site access provided via knox key switch.  Pool exiting also provided with locking arrangement.

6/12/2023 VVitori

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed.

6/12/2023 VVitori

1) During original building review there were multiple questions regarding the illustrated locking arrangements (original comment 9 and 13 shown on plan pages A2.01 and A2.02). To help the project get off the ground we added a hold at 105 framing to get this resolved. The hold read "Thursday, June 17, 2021 Since response doesn't address how sensor/access control door locks will not be locked from egress side of doors when building is occupied, Supervisor advised add hold at framing. Meeting will need to be scheduled with Supervisor, Design Professional and Owner prior to the 105 framing hold to be removed." This meeting has not yet taken place.

This meeting needs to be scheduled prior to REVISION resubmittal of the original door pages that had locking/latching arrangements. Those original door pages will need to be revised clarifying the locking/latching arrangement(s) throughout the property.

Friday, March 24, 2023 at 1p Meeting took place with owner representative and ADT. The Architect was not present. Explained the confusion of their submittal and went over resubmitting. Supervisor Gedris was going to allow just ADT resubmit their pages describing the locking arrangements meeting Code. Held plans in my office for 1 month and then rejected after no submittal.

6/5/2023 VVitori

NOTE:  This submittal is rather confusing to determine which doors are getting which hardware. Some doors have red squares with blue dots, some doors have just blue dots, some have blue dots with push to exit buttons, on 2nd floor there is a red dot by itself. The legend does not address what a blue dot represents.

Also, there are no door labels. This is a problem if I wanted to make a comment regarding a door or a number of doors I have no way to address which door I am referencing.

This can all be addressed by having original door locking/latching hardware plan pages revised to meet the arrangement designed by the property.

6/5/2023 VVitori

6 5 23 Newly added comment based on newly provided information

2) 1 set of plans for 7 clearance sheets (M21-2204, M21-2204*1, M21-2204*2, M21-2204*2, M21-2204*3, M21-2204*4, M21-2204*5, M21-2204*6). This comment will not be signed off until all clearance sheets have all of their comments addressed.

6/12/2023 VVitori