SJC Home
Clearance Sheet M2021-001504*014

 Department IssuesSigned OffIntl

Plan reviewed for Pool, Pool Deck and Pool Fence.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Plans are NOT approved.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

 

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

 

NOTE: Plan Set includes Clearance Sheets M21-1504*13 (Pool Pavilion) and M21-1405*14 (Pool). There are three (3) 12' x 11.4' Cabanas shown on the Pool Deck, NO clearance sheet provided. This review if for the Pool (M21-1504*14).

 

1) There are three (3) 12' x 11.4; cabanas shown on the pool deck and within the plan set. You will need to do either of the following:

a) Remove the cabana's and their references from the plan set, OR

b) Obtain a separate clearance sheet for the three cabanas, OR

c) Have this clearance sheet modified to include the cabanas. 

Friday, June 4, 2021 DF: The clearance sheet was not updated nor was a separate clearance sheet provided.

 

After talking with John Babbitt (06/04/21 at 1454 hrs. ARC3 Architecture) the cabanas will be added to the pool pavilion clearance sheet.

 

2) Identify the pool/pool deck exits. 12:12.2.4

 

3) No door hardware schedule provided. 101:7.2.1

Provide door hardware schedules for the doors and gates. Provide information on any special locking arrangements such as delayed-egress electrical locking systems, sensor-Release of electrical locking systems, mag-locks, etc.

 

4) Provide square footages for the pool and the pool deck area inside the fenced in area and provide the pool (water) and pool deck area (encompassed in by the fence and buildings) occupant load in accordance with NFPA 101 Table 7.3.1.2.

 

5) Will one or more of the pool exits be through the pavilion?

If yes, Show on the plans the exit signage on the pool’s egress side of the pavilion. 

Keep in mind the swing direction of the gates. Page AH102 shows all gates exiting the pool area opening inward save the gate exiting the restroom corridor. 101:12.2.10, 101:7.2.1.4.2

 

6) No normal egress lighting and emergency lighting, exit signage provided for the pool and deck areas.

a) Provide egress and emergency lighting and photometrics and exit signage for the pool deck egress paths. 101:12.2.8, 101:12.2.9, 101:12.2.10

 

7) Show the pool equipment details and identify the pool chemicals in the Pool Equipment Area.. Show tank piping, placement, etc.

NOTE: If the pool chemical tanks are more than 60 gallons a separate Fire Marshal Above/below ground tank will need to be applied for.

 

8) Provide the pool (water area) and the pool deck (total area encompassed in by the fence/buildings).mittal.

 

9) Both the site plan and utility plans show this pavilion to be sprinkled.

Update plans to show Pavilion sprinkled or provide the fire flow of the closest fire hydrant to verify available fire flow.

 

10) No Florida Fire Prevention 7th Edition (FFPC) code analysis provided. 69A-60.002

Provide reference to the FFPC and verify the plans are compliant with the FFPC.