Plan reviewed for 9,370 SF, Type VB construction, 4 unit condo building that is protected with fire sprinklers (13r). 

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC. Reviewed as apartment.

Plans are NOT approved.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Thursday, April 1, 2021 DF: Review of 1st resubmittal.

Plans are APPROVED

Reviewer D. Feagle

4/1/2021 dfeagle

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

4/1/2021 dfeagle

1) The bathtub and shower(s) do not show grab bars. 101:30.2.1.3. Bathtubs, bathtub-shower combinations, or showers are present grab bars shall be provided in accordance with 24.2.8.

Provide exhibits showing compliance with 101:24.2.8 for the bathtubs, bathtub-shower combinations, or showers.

4/1/2021 dfeagle

2) The fire code edition noted in the applicable codes is not correct. FAC 69A-3.012

Update and review the applicable fire code to the 7th Florida Fire Prevention Code 7th ED.

4/1/2021 dfeagle

3) Pages FPS.1, FPS.2, and FPS.3 were not attached to the main plan set.

Before resubmittal, insert the FPS pages into the main plan set.

4/1/2021 dfeagle

4) Only one set of Pages FPS.1, FPS.2, and FPS.3 were submitted.

Provide the second set of Pages FPS.1, FPS.2, and FPS.3 inserted into the plan set.

4/1/2021 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:

- fire alarm system
- fire sprinkler system
- Underground sprinkler system

4/1/2021 dfeagle