Clearance Sheet M2020-000624

 Department IssuesSigned OffIntl

Plan reviewed for installation of a 70 head 13R above ground system system with 13' of underground. Reviewed using FFPC 6th edition effective Dec. 31, 2017.

This plan is approved.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

7/1/2020 dfeagle

Do not forget to:

 

- ID control, drain, and test connection valves with a weatherproof metal or rigid plastic sign. NFPA 13r 5.2.12.4

 

-Include at least 3 spare sprinklers of each type, temperature rating, and orifice size used in the system to be installed on the premises.  NFPA 13r 6.5.1

 

- Call for hydro test to be conducted in accord with NFPA 13. NFPA 13r 6.4.2.1

 

- Have insulation installed at sprinkler final as shown on page FPD.1 to show compliance with NFPA 13r 5.3 and 6.1.4.

 

- Label FDC in accord with NFPA 13r 6.7.4.3

7/1/2020 dfeagle